ZMPT104F
Current-type voltage transformer
Features and application: Small size,high accuracy,good consistency,for voltage and power measurement
Structural parameters:
"*"Same polarity same color same polarity
Front view Bottom view
The main technical parameters:
Model |
ZMPT104F |
Rated input current |
2mA |
Rated output current |
2mA |
turns ratio |
1000:1000 |
phase angle error |
≤45'(input 2mA,sampling resistor 50Ω) |
linear range |
0~1000V 0~6mA(sampling resistor 50Ω) |
linearity |
≤0.2%(20%dot~120%dot) |
Permissible error |
-0.6% ≤ f ≤0%(input 2mA,sampling resistor 50Ω) |
isolation voltage |
3000V |
application |
voltage and power measurement |
Encapsulation |
Epoxy |
installation |
Output leads installation (conventional lead length shown in drawing) |
operating temperature |
-40ºC~+85ºC |
Direction for use:
Figure I FigureII
1. The typical usage of the product is for the active output (FigureI). R'is a limiting resistor,R is a sampling resistor.
2. The product can be directly through the resistance sampling , easy to use ( FigureII).