Zmdct21 100A 0.1 Class DC Immune Current Transformer

Product Details
Customization: Available
Application: Electronic, Instrument, Position Sensor, Audio, Lighting
Type: DC Immune Current Transformer
Still deciding? Get samples of US$ 0/10pcs
Request Sample
Diamond Member Since 2016

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
12000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016
  • Zmdct21 100A 0.1 Class DC Immune Current Transformer
  • Zmdct21 100A 0.1 Class DC Immune Current Transformer
  • Zmdct21 100A 0.1 Class DC Immune Current Transformer
  • Zmdct21 100A 0.1 Class DC Immune Current Transformer
  • Zmdct21 100A 0.1 Class DC Immune Current Transformer
Find Similar Products

Basic Info.

Model NO.
ZMDCT21
Phase
Single
Operation Condition
Indoor
Usage
Protection, Measurement
Winding Form
Multilayer Honeycomb Type
Insulating Medium
Insulating Paper
Installation
Active Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Capacitive Type
Turns Ratio
2500:1
Transport Package
Cartons
Specification
ISO9001, ISO14001, ROHS, CE, SGS
Trademark
zeming
Origin
China
HS Code
8504311000
Production Capacity
1200000PCS/Year

Product Description

100A DC immune Current Transformer  ZMDCT21
 
1.Specification
 
Characteristics Values
Operating frequency 50 Hz ~ 400 Hz
Operating temperature -40ºC ~ 85ºC
Relative  humidity ≤95%
Rated  primary  current Ip 100A
Maximum primary operating current Imax 120A
Testing current for DC component 120A/Root 2 <3%
Rated second current 40mA
Transformation ratio 2500:1
User supplied burden resistor 10ohm
HI-POT (center OD hold to leadwire) 3000Vrms, 1min.
Insulation resistance >500Mohm/500Vdc
Accuracy  class 0.1class

Accuracy class
With the percentage(%)of Ip
5 20 100 120
Ratio Error (±%) 0.4 0.2 0.1 0.1
Phase Displacement(±') 15 8 5 5

2.Dimension
Zmdct21 100A 0.1 Class DC Immune Current Transformer

3.Structure and Size

Zmdct21 100A 0.1 Class DC Immune Current Transformer
Current direction:

Primary current is from K to L, secondary current is from Black line to White line.


4.Material List:
No. Material Spec. model UL code Manufacturer
1 Inner core Nano-crystalline core / ZEMING
2 Outer core Amorphous core / ZEMING
 
3
 
Core shell
 
PBT
 
E238981
QINGDAO QINKE ENGINEE RING PLASTICS CO
LTD
4 Winding 0.13mm, 2500T E258243 ELEKTRISOLA HANGZHOU
CO  LTD
 
5
 
Epoxy resin
TXH-9201-10 epoxy resin in sulating compound  
E196959
TIANJIN XINQIAO INSULATI NG MATERIAL
CO  LTD
 
6
 
Leading wire
UL1007, 26AWG,
Black&White
 
E315651
ZHEJIANG CHENGBAO WIR E & CABLE CO
LTD
7 Case Black E238981 QINGDAO QINKE ENGINEE
RING PLASTICS CO LTD
8 Connector Molex 5264-2P / Shenzhen Pinshang Electronic
 
9
 
Tape
Flame retardant, Environmental protection  
E165111
JINGJIANG YAHUA PRESSURE SENSITIVE
GLUE CO LTD


Zmdct21 100A 0.1 Class DC Immune Current Transformer
Zmdct21 100A 0.1 Class DC Immune Current Transformer
Zmdct21 100A 0.1 Class DC Immune Current Transformer
Zmdct21 100A 0.1 Class DC Immune Current Transformer
Zmdct21 100A 0.1 Class DC Immune Current Transformer
Zmdct21 100A 0.1 Class DC Immune Current Transformer

Zmdct21 100A 0.1 Class DC Immune Current TransformerZmdct21 100A 0.1 Class DC Immune Current TransformerZmdct21 100A 0.1 Class DC Immune Current TransformerZmdct21 100A 0.1 Class DC Immune Current Transformer
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier