Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter

Product Details
Customization: Available
Application: Electronic, Instrument, Position Sensor, Audio, Lighting
Type: DC Immune Current Transformer
Still deciding? Get samples of US$ 0/10pcs
Request Sample
Diamond Member Since 2016

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
12000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016
  • Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
  • Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
  • Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
  • Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
Find Similar Products

Basic Info.

Model NO.
ZMDCT05
Phase
Single
Operation Condition
Indoor
Usage
Protection, Measurement
Winding Form
Multilayer Honeycomb Type
Insulating Medium
Insulating Paper
Installation
Active Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Capacitive Type
Turns Ratio
2500:1
Transport Package
Cartons
Specification
ISO9001, ISO14001, ROHS, CE, SGS
Trademark
zeming
Origin
China
HS Code
8504311000
Production Capacity
1200000PCS/Year

Product Description

40A DC immune Current Transformer  ZMDCT05
 
1.Specification
 
Characteristics Values
Operating frequency 50 Hz ~ 400 Hz
Operating temperature -40ºC ~ 85ºC
Relative humidity ≤95%
Rated primary current  Ip 40A
Maximum primary operating current Imax 48A
Testing current for DC component 40A/Root 2 <3%
Rated second current 16mA
Transformation ratio 1:2500
User supplied burden resistor 10Ω
Accurate operating current range 1.66%Ip~Imax
INPUT: 2.5A R:100Ω, f: 60HZ OUTPUT: 99.5~100mV
Power frequency withstand voltage 3Kv/1min
Insulation resistance >500MΩ/500Vdc
Interturn insulation 40A/1min
Accuracy class 0.2class
 
Accuracy class With the percentage(%)of Ip
1.66 5 20 100 120
Ratio Error (±%) 0.2 0.2 0.2 0.2 0.2
Phase Displacement(±·) 12 12 12 12 12


2.Structure and Size

Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
Current direction:


Primary current is from K to L, secondary current is from Black line to White line.

3.Dimension
 
Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter

4.Material List
No. Material Spec. model UL code Manufacturer
1 Inner core Nano-crystalline  core / ZEMING
2 Outer core Amorphous core / ZEMING
3 Core shell PBT E238981 QINGDAO QINKE ENGINEERING PLASTICS
4 Winding 2500T E258243 ELEKTRISOLA HANGZHOU CO LTD
5 Outside shell Black E238981 QINGDAO QINKE ENGINEERING PLASTICS
6 Epoxy resin TXH-9201-10 epoxy resin insulating compound E196959 TIANJIN XINQIAO INSULATING MATERIAL CO
7 Leading wire UL1007, 26AWG,
Black&White
E315651 ZHEJIANG CHENGBAO WIRE & CABLE
9 Connector Molex 5264-2P / Shenzhen Pinshang Electronic
10 Tape Flame retardant,
Environmental protection
E165111 JINGJIANG YAHUA PRESSURE SENSITIVE
GLUE CO LTD
Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter
Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter


Zmdct05 0.2 Class 40A DC Immune Current Transformer for Energy MeterZmdct05 0.2 Class 40A DC Immune Current Transformer for Energy MeterZmdct05 0.2 Class 40A DC Immune Current Transformer for Energy MeterZmdct05 0.2 Class 40A DC Immune Current Transformer for Energy Meter

Send your message to this supplier