ZMCT118F Current Transformer
Features and application: Small size,high accuracy,good consistency,for current and power measurement
Structural parameters:
1,2pin: secondary output,3,4pin: empty pin
Front view Bottom view
The main technical parameters:
model |
ZMCT118F |
input current |
0~30A(sampling resistor 50Ω) |
Rated output current |
5mA at 5A |
turns ratio |
1000:1 |
phase angle error |
≤15'(input 5A,sampling resistor 50Ω) |
linear range |
0~30A(sampling resistor 50Ω) |
linearity |
≤0.3%(5%dot~120%dot) |
Permissible error |
-0.3%≤ f ≤+0.3%(input 5A,sampling resistor 50Ω) |
isolation voltage |
4500V |
application |
Precise measurement of current and power |
Encapsulation |
Epoxy |
installation |
PCB mounting(Pin length>3mm) |
operating temperature |
-40ºC~+85ºC |
Direction for use:
Figure I FigureII
1. ZMCT118F used for measurement. Typical usage is shown in Figure 1 and Figure 2.
R is a sampling resistor.
2. Empty pin can not be grounded.